| SPECIFICATIONS
Electrolyte at 77F (25C): 1.300 specific gravity nominal sulfuric acid
System float voltages: 2.25 - 2.27 Volts per cell
Life expectancy: 10 years, full float service at 77F (25C)
Container and cover: High-impact, flame-retardant PVC Flammability ratings: UL 94-VO; ASTM D-635, self extinguishing Oxygen index > 32
Safety vent system Low-pressure release valve with flash arrester
Note: AC Ripple current from the charger shall not exceed 5 percent of the 8-hour (ampere-hour) rating of the battery.
FEATURES AND BENEFITS
Patented post seal design with secondary epoxy seal to increase integrity
- Leak-free operation
- Superior reliability
Two-fold vent system
- Low-pressure safety valve with flash arrester
- Minimizes bulging
- Prevents flashback explosion from external ignition source
Thick radial grid design for both positive and negative plates
- Improves current carrying capacity and performance
- Long float life
Immobilized electrolyte technology
- Absorbent glass mat design (AGM)
- Safe handling and storage
Advanced, computer-controlled thermal cover-to-jar weld
- Greater reliability and consistency
PVC container and cover
- Provides excellent water vapor retention, preventing dry out
- Prevents oxygen infiltration
- High-impact resistance
Through-the-partition intercell connection
- Shortens current paths
- Increases performance
Copper-to-copper connections
- Minimize resistance drop, especially at high rates
- Reduce need for retorquing connections
Measurable quality and outstanding performance
- 100 percent of cells tested for conductance voltage and capacity
- Tested in accordance with Bellcore TR-NWT-000766 specifications
- 100 percent of cells tested to 95 percent capacity at the 8-hour rate to 1.75 Vpc.
Automated, state-of-the-art, cast-on strap process
- Ensures consistent, high-quality, low electrical - resistance welds
|